Echo LSIS Control

Manual Motor Starters Technical Information Manual Motor Controller (UL508)

MMS 32H ●

MMS 63H ● 50 65

MMS 100H ● 75 100

Rated operational current Іe Max. short-circuit current 240V

[A]

17 22 32 40

100 30 10

100 30 10

100 30 10

100 50 10

100 50 10

[kA] [kA] [kA] [HP] [HP] [HP] [HP] [HP] [HP]

100 30 10

100 50 10

100 50 10

480V 600V

Motor load

In case of 1-phase use in series as shown below

3 7.5

2 5 7.5

1.5 3 5 7.5

5 10 20 20 40 60

10 20 30 30 75

1 Phase 115V

1 3 3 5

5 10 20 20 40 60

5 15 20 25 50 60

230V

10 10 30 30

3 Phase 200V

10 20 30

230V 460V 575V

15 20 80 80

10 15 60 60

100 400 400

150 150

125 125

250 250

Max. fuse size

[A] [A]

250 250

350 350

Max. breaker size

Type '2' coordination according to IEC 947-4-1

Short-circuit current Iq = 50kA Voltage : 400/415V, 50/60Hz

Manual motor starter

Standard motors AC-3

Thermal overload Magnetic release

Contactor

at 400/415V

Circuit breaker

release

response current

setting range

1500rpm

[kW] 7.5

[A]

Type

[A]

[A]

Type

[A]

15.5

MMS-32H 17A MMS-32H 22A MMS-32H 32A MMS-63H 40A MMS-100S 75A MMS-100S 100A

11~17 14~22 22~32 28~40 55~75

221 286 416 520 975

GMC-22 GMC-32 GMC-32 GMC-50 GMC-75 GMC-85

22 32 32 50 75 85

10 15

20 29 35 67 80

18.5

37 45

80~100

1300

Definition type '2' coordination according to IEC 947-4-1 : The contactor or the starter must not endanger persons or systems in the event of a short-circuit. The contactor or the starter must be suitable for further use. No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts provided that these can be easily separated without significant deformation (such as with a screwdriver). • • •

7