Manual Motor Starters Technical Information IEC performance data (Motor protection)

High breaking type MMS 32H Rated operational current Іe ●

MMS 63H ● 50 65

MMS 100H ● 75 100

[A]

17

22 32 40

Switching of standard three-phase motors AC-2, AC-3 230/240V

4 7.5 7.5 7.5 7.5 15 1.8 11 11 18.5 22 11 15 22 30

11 15 22 30 30 37 45 55

22 30 37 45 45 63 63 90

[kW] 3.7/4

400/415V

[kW] [kW] [kW]

500V 690V

Back-up fuses gG, gL,, only if Іcc>Іcu ( * = No back up fuse required) 230/240V

* * 100 125 125 160 80 100 100 125 80 80 80 100 63 63 63 80 100 100 100 100 50 50 50 40 20 20 20 15 10 10 10 8 4 4 4 3 * * 100 100 100 100 38 38 38 30 15 15 15 11 8 8 8 6 4 4 4 3

* * 160 160 125 160 100 100 80 80 100 75 50 35 35 25 10 6 5 3 100 50 50 27 27 19 8 5 5 3

* *

*

[A] [A] [A]

* 200 200 160 160 125 160 100 100 75 75 50 50 12 12 6 6

400/415V 440/460V

V005

]A[ ]A[

V096 Ultimate short-circuit breaking capacity Іcu 230/240V

[kA] [kA] [kA] [kA] [kA] [kA] [kA] [kA] [kA] [kA]

400/415V 440/460V

500V 690V

Rated service short-circuit breaking capacity Іcs 230/240V

100 100 50 50 38 38

400/415V 440/460V

9 9 6 6

500V 690V

Note) * = Short circuit proof up to 50 or 100kA. No back up fuse required.

Manual motor controller (UL 508, CSA C22.2 as Manual motor controllers)

Combination Motor Controller - Group lnstallation - Type E starter

MMS 63H ● 50 65

MMS 100H ● 75 100

MMS 32H ●

Rated operational current Іe Max. short-circuit current 240V

[A]

17

22 32 40

100 30 10

100 30 10

100 30 10

100 50 10

100 50 10

[kA] [kA] [kA]

100 30 10

100 50 10

100 50 10

480V 600V

Motor load

In case of 1-phase use in series as shown below

1 1.5 2 3 3 3 5 7.5 3 5 7.5 10 5 7.5 10 10 10 15 20 30 15 20 30 30

1 Phase 115V

[HP] [HP] [HP] [HP] [HP] [HP]

3 5 10 10 20 20 20 20 40 40 60 60

5 10 15 20 20 30 25 30 50 75 60 100

230V

3 Phase 200V

230V 460V 575V

Maximum rated current

500 500 500 500

[A]

600 600

1000 1000

of fuse or breaker

6